Conduit Fill Chart and Calculator
Conduit fill is the share of the conduit's inside area the wires take up, limited to 53% for one wire, 31% for two and 40% for three or more. For example, 13 twelve-gauge THHN/THWN-2 wires fit in a 3/4 inch EMT conduit by this method.
Last verified October 5, 2026
Fill result
Quick reference: THHN/THWN-2 wires in EMT
Most conductors of one size at 40% fill, trade sizes 1/2 to 2 inch.
The usual fill rule limits the wires to 53% of the conduit's internal area for one conductor, 31% for two and 40% for three or more. This page works out the area of the conduit and of each wire from the manufacturer dimensions below, then counts how many wires fit under the limit.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" |
|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 10 | 18 | 30 | 52 | 72 | 118 |
| 12 AWG | 0.140 | 7 | 13 | 22 | 38 | 52 | 87 |
| 10 AWG | 0.170 | 5 | 9 | 15 | 26 | 35 | 59 |
| 8 AWG | 0.230 | 2 | 5 | 8 | 14 | 19 | 32 |
| 6 AWG | 0.254 | 2 | 4 | 6 | 11 | 16 | 26 |
| 4 AWG | 0.330 | 1 | 2 | 4 | 6 | 9 | 15 |
| 3 AWG | 0.360 | 1 | 2 | 3 | 5 | 8 | 13 |
| 2 AWG | 0.390 | 1 | 1 | 2 | 5 | 6 | 11 |
Quick reference: THHN/THWN-2 wires in PVC Schedule 40
Same limit and wire sizes, using the minimum inside diameter that PVC makers publish.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" |
|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 9 | 16 | 28 | 49 | 67 | 113 |
| 12 AWG | 0.140 | 6 | 12 | 20 | 36 | 49 | 83 |
| 10 AWG | 0.170 | 4 | 8 | 13 | 24 | 33 | 56 |
| 8 AWG | 0.230 | 2 | 4 | 7 | 13 | 18 | 30 |
| 6 AWG | 0.254 | 2 | 3 | 6 | 11 | 15 | 25 |
| 4 AWG | 0.330 | 1 | 2 | 3 | 6 | 8 | 15 |
| 3 AWG | 0.360 | 1 | 1 | 3 | 5 | 7 | 12 |
| 2 AWG | 0.390 | 0 | 1 | 2 | 4 | 6 | 10 |
Conduit dimensions used
| Conduit type | Trade size | Inside diameter used (in) | ID basis | Internal area (in²) | One wire, 53% (in²) | Two wires, 31% (in²) | Three or more, 40% (in²) |
|---|---|---|---|---|---|---|---|
| EMT | 1/2" | 0.622 | nominal ID | 0.304 | 0.161 | 0.094 | 0.122 |
| EMT | 3/4" | 0.824 | nominal ID | 0.533 | 0.283 | 0.165 | 0.213 |
| EMT | 1" | 1.049 | nominal ID | 0.864 | 0.458 | 0.268 | 0.346 |
| EMT | 1-1/4" | 1.380 | nominal ID | 1.496 | 0.793 | 0.464 | 0.598 |
| EMT | 1-1/2" | 1.610 | nominal ID | 2.036 | 1.079 | 0.631 | 0.814 |
| EMT | 2" | 2.067 | nominal ID | 3.356 | 1.778 | 1.040 | 1.342 |
| PVC Schedule 40 | 1/2" | 0.578 | minimum ID | 0.262 | 0.139 | 0.081 | 0.105 |
| PVC Schedule 40 | 3/4" | 0.780 | minimum ID | 0.478 | 0.253 | 0.148 | 0.191 |
| PVC Schedule 40 | 1" | 1.004 | minimum ID | 0.792 | 0.420 | 0.245 | 0.317 |
| PVC Schedule 40 | 1-1/4" | 1.335 | minimum ID | 1.400 | 0.742 | 0.434 | 0.560 |
| PVC Schedule 40 | 1-1/2" | 1.564 | minimum ID | 1.921 | 1.018 | 0.596 | 0.768 |
| PVC Schedule 40 | 2" | 2.021 | minimum ID | 3.208 | 1.700 | 0.994 | 1.283 |
Wire dimensions used
Insulated wire diameters differ between manufacturers. The calculator and the tables use the largest published value, which gives the lower conductor count.
| Wire size | Cerrowire - THHN/THWN-2 spec sheet | Prysmian - THHN/THWN-2 High Speed SPEC 5290 | Encore Wire - SuperSlick Elite THHN spec sheet | Southwire - product pages THHN/THWN 14/12/10 AWG stranded | Priority Wire & Cable - Copper THHN/THWN-2 spec | Southwire - SIMpull THHN/THWN-2 SPEC 10000 | Largest (used) |
|---|---|---|---|---|---|---|---|
| 14 AWG | 0.111 | 0.109 | 0.109 | 0.113 | 0.120 | — | 0.120 |
| 12 AWG | 0.130 | 0.130 | 0.128 | 0.132 | 0.140 | — | 0.140 |
| 10 AWG | 0.164 | 0.161 | 0.161 | 0.165 | 0.170 | — | 0.170 |
| 8 AWG | 0.216 | 0.212 | 0.213 | — | 0.230 | 0.217 | 0.230 |
| 6 AWG | 0.254 | 0.248 | 0.249 | — | 0.250 | 0.253 | 0.254 |
| 4 AWG | 0.324 | 0.317 | 0.318 | — | 0.330 | 0.322 | 0.330 |
| 3 AWG | 0.352 | — | 0.346 | — | 0.360 | 0.350 | 0.360 |
| 2 AWG | 0.384 | 0.375 | 0.378 | — | 0.390 | 0.384 | 0.390 |
| 1 AWG | 0.446 | 0.427 | 0.435 | — | 0.450 | 0.441 | 0.450 |
| 1/0 AWG | 0.486 | 0.466 | 0.474 | — | 0.500 | 0.480 | 0.500 |
| 2/0 AWG | 0.532 | 0.509 | 0.518 | — | 0.540 | 0.524 | 0.540 |
| 3/0 AWG | 0.584 | 0.557 | 0.568 | — | 0.600 | 0.574 | 0.600 |
| 4/0 AWG | 0.642 | 0.612 | 0.624 | — | 0.660 | 0.627 | 0.660 |
| 250 kcmil | 0.711 | 0.694 | — | — | 0.720 | 0.684 | 0.720 |
| 300 kcmil | 0.766 | 0.747 | — | — | 0.766 | 0.753 | 0.766 |
| 350 kcmil | 0.817 | 0.797 | — | — | 0.830 | 0.803 | 0.830 |
| 400 kcmil | 0.864 | 0.842 | — | — | 0.864 | 0.848 | 0.864 |
| 500 kcmil | 0.949 | 0.925 | — | — | 0.960 | 0.931 | 0.960 |
| 600 kcmil | 1.051 | 1.024 | — | — | 1.051 | 1.030 | 1.051 |
| 750 kcmil | 1.156 | 1.126 | — | — | 1.170 | 1.132 | 1.170 |
| 1000 kcmil | 1.310 | 1.275 | — | — | 1.320 | 1.281 | 1.320 |
How to use this chart
Use the calculator to add each wire size and count, then read the percentage full and whether it fits. The quick-reference tables list the most wires of a single size that fit each trade size at the 40% limit. Conduit and wire areas are worked out from manufacturer dimensions, and where manufacturers publish different wire diameters the largest value is used, which gives the lower wire count. Compare the answer with the adopted code table before you buy wire.
Frequently asked questions
How many 12 AWG wires fit in 1/2 inch EMT?
By this method, 7 twelve-gauge THHN/THWN-2 wires fit in 1/2 inch EMT at the 40% limit. The code table may allow a different count because it uses its own wire areas.
How many 12 AWG wires fit in 3/4 inch EMT?
13 wires at the 40% limit, using the largest published wire diameter.
What are the conduit fill percentages?
One conductor may fill 53% of the conduit area, two conductors 31% and three or more 40%.
Does it matter which wire type I use?
Yes. Insulation thickness changes the wire diameter, so THHN/THWN-2 and XHHW-2 of the same gauge take different space. The calculator has both.
Why does PVC hold fewer wires than EMT of the same trade size?
PVC conduit has thicker walls, so its inside diameter is smaller. Schedule 80 has thicker walls than Schedule 40 and holds fewer still.
Should I fill conduit to the limit?
Not if you can avoid it. Long pulls, bends and bundled wires are easier with room to spare, so sizing up one trade size is common practice.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.