Voltage Drop Calculator
Voltage drop is the voltage lost along a wire. For example, 16 amps through 100 feet of 12 AWG copper at 120 volts drops about 6.32 volts, or 5.3%.
Last verified October 5, 2026
Important. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician.
Voltage drop
The formula
Single-phase drop in volts is 2 × K × I × L ÷ CM. Three-phase replaces the 2 with 1.732. K is the resistivity constant in ohm-circular-mils per foot: 12.9 for copper and 21.2 for aluminum at 75°C. I is the current in amps, L is the one-way length in feet, and CM is the wire's circular mils. Percent drop is the drop divided by the source voltage.
A common rule of thumb keeps a branch circuit under 3% and the whole run from panel to load under 5%. Those limits are guidance for efficiency, not a safety rating.
How to use this calculator
Enter the source voltage, load current, one-way length and wire size, then pick the metal and single or three-phase. The calculator gives the drop in volts and percent, the voltage at the load, and flags results above the common 3% and 5% guidelines. If the drop is too high, move to the next larger wire size and try again. Length means one way, from the source to the load, because the formula already counts the return path.
Frequently asked questions
How do you calculate voltage drop?
For single-phase, drop in volts is 2 times K times current times one-way length divided by the wire circular mils. K is 12.9 for copper and 21.2 for aluminum.
What is an acceptable voltage drop?
A common guideline is 3% on a branch circuit and 5% total from the panel to the farthest load.
How do I fix too much voltage drop?
Use a thicker wire, shorten the run, raise the voltage or lower the current. Thicker wire is the usual fix.
Is voltage drop different for three-phase?
Yes. The formula uses 1.732 in place of 2, so a three-phase circuit loses less voltage than a single-phase circuit at the same current and length.
Does the length mean one way or round trip?
One way. The formula already counts the return conductor, so enter the distance from the source to the load.
Does temperature change voltage drop?
Yes. Wire resistance rises as it warms. The K values on this page are for 75 C, which is a reasonable working temperature.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.