Wire Gauge Amp Chart

Allowable current depends on the wire gauge, the metal and the insulation temperature rating. For example, 12 AWG copper is rated for 25 amps in the 75 C column, though its breaker limit is 20 amps.

Last verified October 5, 2026

Download PDF
Wire gauge lookup

Quick lookup

0.08 mm

40 AWG wire

Diameter
0.0031 in (0.080 mm)
Area
0.005 mm² (10 circular mils)
Copper resistance
1048.8392 Ω per 1,000 ft at 20°C

Wire gauge amp chart: copper and aluminum, 14 AWG to 4/0

Allowable current by insulation temperature rating. Small copper wire is also limited by its overcurrent protection: 15 A for 14 AWG, 20 A for 12 AWG and 30 A for 10 AWG.

Wire sizeCopper 60°C (A)Copper 75°C (A)Copper 90°C (A)Aluminum 60°C (A)Aluminum 75°C (A)Aluminum 90°C (A)
14 AWG152025———
12 AWG202530—2025
10 AWG303540—3035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115—7585
2 AWG951151307590100
1 AWG11013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205

What the dashes mean

A dash is a value we left out because it did not meet our two-source rule. It is not zero.

  • Aluminum 60°C, 12 AWG and 10 AWG. Only distributors repeat these. No second manufacturer prints a 60°C aluminum column for them.

How to use this chart

Find the wire size and read the column that matches your insulation temperature, which is printed on the wire. Use the lower of the wire rating and the temperature rating of the terminals it connects to, which is usually 60 C or 75 C. A dash means we left the value out because it did not meet our two-source rule. The numbers are a guideline from manufacturer literature, so check the adopted code for your install.

Frequently asked questions

How many amps can 12 AWG wire carry?

The wire is rated 20 A at 60 C, 25 A at 75 C and 30 A at 90 C for copper, but 12 AWG circuits are limited to a 20 amp breaker.

How many amps can 10 AWG wire carry?

Copper 10 AWG is rated 30 A at 60 C, 35 A at 75 C and 40 A at 90 C, with a 30 amp breaker limit.

How many amps can 14 AWG wire carry?

Copper 14 AWG is rated 15 A at 60 C, 20 A at 75 C and 25 A at 90 C, with a 15 amp breaker limit.

Does aluminum wire carry less than copper?

Yes. At the same gauge, aluminum is rated for roughly 80% to 85% of what copper carries. Aluminum also needs terminals rated for it.

Which temperature column should I use?

Use the column for the lowest temperature rating among the wire, the breaker and the terminals. For most home panels that is 60 C or 75 C.

Why are some aluminum values missing?

We could not confirm the 60 C aluminum rating for 12 AWG and 10 AWG from two manufacturers, so we left those two values out.

Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.

Last verified October 5, 2026. How we verify explains our two-source rule and what we leave out.

Aluminum 60°C values for 12 AWG and 10 AWG are left out because only distributors that restate the electrical code print them. One Southwire SEU aluminum data sheet prints 30 A at 8 AWG where other manufacturers print 35 A.

Sources used on this page
  • NIST Handbook 100 (copper resistivity)
  • Southwire spec sheets
  • ASTM B3 (via iTeh Standards)
  • Cerro Wire
  • Southwire SPEC 10003 THHN/THWN
  • Lapp Tannehill ampacity chart
  • Ramcorp Wire & Cable wire ampacity chart
  • Southwire HVAC catalog
  • Southwire SPEC 10000 Building Wire
  • FRCABLE wire ampacity chart
  • Southwire SPEC 10015 SIMpull XHHW-2 Aluminum AlumaFlex