Wire Size Calculator

The wire size calculator finds the smallest wire that carries your load and keeps voltage drop within your limit. For example, a 20 amp load 100 feet from a 120 volt source with a 3% limit needs 8 AWG copper.

Last verified October 5, 2026

Important. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician.

Wire size calculator

Smallest wire that works

10 AWG

How the answer is worked out

The calculator checks two limits and returns the larger wire. First, the wire must carry the load: it uses the 75°C ampacity column for copper or aluminum building wire, and caps 14, 12 and 10 AWG copper at 15, 20 and 30 amps. Second, the voltage drop over the run must stay under your limit, using drop = 2 × K × I × L ÷ CM for single-phase (1.732 for three-phase), where K is 12.9 for copper and 21.2 for aluminum at 75°C.

How to use this calculator

Enter the current, voltage, one-way length and the voltage drop you will accept, then choose the metal and single or three-phase. The calculator checks the ampacity of each size in the 75 C column and its voltage drop over the run, and returns the smallest size that passes both. The page also shows the next size down and why it fails. Treat the answer as a planning number, and have the circuit checked by a licensed electrician.

Frequently asked questions

What size wire do I need for 100 feet at 20 amps?

At 120 volts with a 3% drop limit, 8 AWG copper. The current alone would allow 12 AWG, but the voltage drop is too high.

What size wire do I need for a 30 amp, 240 volt circuit?

For short runs, 10 AWG copper carries the current. Longer runs may need thicker wire, so enter your distance in the calculator.

How is the wire size worked out?

The calculator applies two limits. The wire must carry the current in the 75 C column, and voltage drop, equal to 2 times K times current times length divided by circular mils, must stay under your limit.

What is a good voltage drop limit?

A common rule of thumb is 3% on a branch circuit and 5% for the whole run from the panel to the load.

Is aluminum wire a good choice for long runs?

It can be cheaper, but it needs larger conductors than copper for the same current, and terminals and breakers rated for aluminum.

Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.

Last verified October 5, 2026. How we verify explains our two-source rule and what we leave out.

Aluminum 60°C values for 12 AWG and 10 AWG are left out because only distributors that restate the electrical code print them. One Southwire SEU aluminum data sheet prints 30 A at 8 AWG where other manufacturers print 35 A.

Sources used on this page
  • Cerro Wire
  • Southwire SPEC 10003 THHN/THWN
  • Lapp Tannehill ampacity chart
  • Ramcorp Wire & Cable wire ampacity chart
  • Southwire HVAC catalog
  • Southwire SPEC 10000 Building Wire
  • FRCABLE wire ampacity chart
  • Southwire SPEC 10015 SIMpull XHHW-2 Aluminum AlumaFlex
  • NIST Handbook 100
  • Southwire Power Cable Manual