Wire Gauge Chart (AWG)

AWG is the American Wire Gauge, where a smaller number means thicker wire. For example, 12 AWG is 0.0808 inch (2.053 mm) across, and 10 AWG is 0.1019 inch.

Last verified October 5, 2026

Download PDF
Wire gauge lookup

Quick lookup

0.08 mm

40 AWG wire

Diameter
0.0031 in (0.080 mm)
Area
0.005 mm² (10 circular mils)
Copper resistance
1048.8392 Ω per 1,000 ft at 20°C

AWG wire gauge chart, 40 AWG to 1000 kcmil

Diameter = 0.005 × 92^((36 − AWG) ÷ 39) inches. Resistance uses the annealed copper standard of 10.371 Ω·circular-mil per foot at 20°C.

AWGDiameter (in)Diameter (mm)Area (mm²)Circular milsCopper Ω per 1,000 ftCopper Ω per kmCopper lb per 1,000 ft
400.00310.0800.005101048.83923441.0740.0
390.00350.0900.00612831.76732728.8950.0
380.00400.1010.00816659.62142164.1120.0
370.00450.1130.01020523.10361716.2190.1
360.00500.1270.01325414.84001361.0240.1
350.00560.1430.01632328.98311079.3410.1
340.00630.1600.02040260.8954855.9560.1
330.00710.1800.02550206.8995678.8040.2
320.00800.2020.03263164.0788538.3160.2
310.00890.2270.04080130.1204426.9040.2
300.01000.2550.051101103.1901338.5500.3
290.01130.2860.06412781.8335268.4830.4
280.01260.3210.08116064.8969212.9160.5
270.01420.3610.10220251.4656168.8500.6
260.01590.4050.12925440.8141133.9040.8
250.01790.4550.16232032.3670106.1911.0
240.02010.5110.20540425.668284.2131.2
230.02260.5730.25850920.355866.7841.5
220.02530.6440.32664216.142952.9621.9
210.02850.7230.41081012.801942.0012.5
200.03200.8120.5181,02210.152433.3083.1
190.03590.9120.6531,2888.051226.4153.9
180.04031.0240.8231,6246.384920.9484.9
170.04531.1501.0382,0485.063416.6126.2
160.05081.2911.3092,5834.015513.1747.8
150.05711.4501.6503,2573.184410.4489.9
140.06411.6282.0814,1072.52548.28512.4
130.07201.8282.6245,1782.00276.57115.7
120.08082.0533.3096,5301.58825.21119.8
110.09072.3054.1728,2341.25954.13224.9
100.10192.5885.26110,3830.99883.27731.4
90.11442.9066.63413,0930.79212.59939.6
80.12853.2648.36616,5100.62822.06150.0
70.14433.66510.54920,8180.49821.63463.0
60.16204.11513.30226,2510.39511.29679.5
50.18194.62116.77333,1020.31331.028100.2
40.20435.18921.15141,7410.24850.815126.4
30.22945.82726.67052,6350.19700.646159.3
20.25766.54433.63166,3710.15630.513200.9
10.28937.34842.40883,6930.12390.407253.3
1/00.32498.25153.475105,5350.09830.322319.5
2/00.36489.26667.431133,0770.07790.256402.8
3/00.409610.40585.029167,8060.06180.203508.0
4/00.460011.684107.219211,6000.04900.161640.5
250 kcmil0.500012.700126.677250,0000.04150.136756.8
300 kcmil0.547713.912152.012300,0000.03460.113908.1
350 kcmil0.591615.027177.348350,0000.02960.0971059.5
400 kcmil0.632516.064202.683400,0000.02590.0851210.8
500 kcmil0.707117.961253.354500,0000.02070.0681513.6
600 kcmil0.774619.675304.024600,0000.01730.0571816.3
700 kcmil0.836721.251354.695700,0000.01480.0492119.0
750 kcmil0.866021.997380.031750,0000.01380.0452270.3
800 kcmil0.894422.718405.366800,0000.01300.0432421.7
900 kcmil0.948724.097456.037900,0000.01150.0382724.4
1000 kcmil1.000025.400506.7071,000,0000.01040.0343027.1

Copper and aluminum ampacity guideline, 14 AWG to 4/0

A guideline from manufacturer literature for insulated building wire with no more than three current-carrying conductors in a raceway. The adopted electrical code governs.

Wire sizeCopper 60°C (A)Copper 75°C (A)Copper 90°C (A)Aluminum 60°C (A)Aluminum 75°C (A)Aluminum 90°C (A)
14 AWG152025———
12 AWG202530—2025
10 AWG303540—3035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100115—7585
2 AWG951151307590100
1 AWG11013014585100115
1/0125150170100120135
2/0145175195115135150
3/0165200225130155175
4/0195230260150180205

How to use this chart

Find the gauge in the first column and read across for diameter, area, circular mils and copper resistance. Use the lookup for one size at a time. The ampacity table below the chart is a guideline for copper and aluminum building wire, which depends on insulation rating, so match it to your wire's label. For a calculation of what size to use for a load and a distance, see the wire size calculator.

Frequently asked questions

What is the diameter of 12 AWG wire?

0.0808 inch, or 2.053 mm, for a solid conductor.

What is the resistance of 12 AWG copper wire?

About 1.59 ohms per 1,000 feet at 20 C.

What does a smaller AWG number mean?

Thicker wire. Every 3 steps roughly doubles the area, and every 6 steps doubles the diameter.

What is kcmil?

One thousand circular mils. It is the unit used for large wire above 4/0, like 250 kcmil and 500 kcmil.

What size wire do I need for 20 amps?

12 AWG copper is the usual choice for a 20 amp circuit. Long runs may need thicker wire to keep voltage drop in check.

How is the AWG diameter calculated?

Diameter in inches is 0.005 times 92 raised to the power of (36 minus the gauge number) divided by 39.

Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.

Last verified October 5, 2026. How we verify explains our two-source rule and what we leave out.

Aluminum 60°C values for 12 AWG and 10 AWG are left out because only distributors that restate the electrical code print them. One Southwire SEU aluminum data sheet prints 30 A at 8 AWG where other manufacturers print 35 A.

Sources used on this page
  • NIST Handbook 100 (copper resistivity)
  • Southwire spec sheets
  • ASTM B3 (via iTeh Standards)
  • Cerro Wire
  • Southwire SPEC 10003 THHN/THWN
  • Lapp Tannehill ampacity chart
  • Ramcorp Wire & Cable wire ampacity chart
  • Southwire HVAC catalog
  • Southwire SPEC 10000 Building Wire
  • FRCABLE wire ampacity chart
  • Southwire SPEC 10015 SIMpull XHHW-2 Aluminum AlumaFlex