EMT Conduit Fill Chart
EMT is thin-wall steel electrical tubing. At the 40% limit, 1/2 inch EMT holds 7 twelve-gauge wires and 3/4 inch holds 13, by this method.
Last verified October 5, 2026
Fill result
EMT conduit fill chart, 1/2 to 4 inch
Most THHN/THWN-2 conductors of one size at 40% fill.
The usual fill rule limits the wires to 53% of the conduit's internal area for one conductor, 31% for two and 40% for three or more. This page works out the area of the conduit and of each wire from the manufacturer dimensions below, then counts how many wires fit under the limit.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 3-1/2" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 10 | 18 | 30 | 52 | 72 | 118 | 207 | 312 | 408 | 521 |
| 12 AWG | 0.140 | 7 | 13 | 22 | 38 | 52 | 87 | 152 | 229 | 299 | 383 |
| 10 AWG | 0.170 | 5 | 9 | 15 | 26 | 35 | 59 | 103 | 155 | 203 | 259 |
| 8 AWG | 0.230 | 2 | 5 | 8 | 14 | 19 | 32 | 56 | 85 | 111 | 142 |
| 6 AWG | 0.254 | 2 | 4 | 6 | 11 | 16 | 26 | 46 | 69 | 91 | 116 |
| 4 AWG | 0.330 | 1 | 2 | 4 | 6 | 9 | 15 | 27 | 41 | 53 | 68 |
| 3 AWG | 0.360 | 1 | 2 | 3 | 5 | 8 | 13 | 23 | 34 | 45 | 57 |
| 2 AWG | 0.390 | 1 | 1 | 2 | 5 | 6 | 11 | 19 | 29 | 38 | 49 |
| 1 AWG | 0.450 | 0 | 1 | 2 | 3 | 5 | 8 | 14 | 22 | 29 | 37 |
| 1/0 AWG | 0.500 | 0 | 1 | 1 | 3 | 4 | 6 | 11 | 18 | 23 | 30 |
| 2/0 AWG | 0.540 | 0 | 0 | 1 | 2 | 3 | 5 | 10 | 15 | 20 | 25 |
| 3/0 AWG | 0.600 | 0 | 0 | 1 | 2 | 2 | 4 | 8 | 12 | 16 | 20 |
| 4/0 AWG | 0.660 | 0 | 0 | 1 | 1 | 2 | 3 | 6 | 10 | 13 | 17 |
EMT dimensions used
| Conduit type | Trade size | Inside diameter used (in) | ID basis | Internal area (in²) | One wire, 53% (in²) | Two wires, 31% (in²) | Three or more, 40% (in²) |
|---|---|---|---|---|---|---|---|
| EMT | 1/2" | 0.622 | nominal ID | 0.304 | 0.161 | 0.094 | 0.122 |
| EMT | 3/4" | 0.824 | nominal ID | 0.533 | 0.283 | 0.165 | 0.213 |
| EMT | 1" | 1.049 | nominal ID | 0.864 | 0.458 | 0.268 | 0.346 |
| EMT | 1-1/4" | 1.380 | nominal ID | 1.496 | 0.793 | 0.464 | 0.598 |
| EMT | 1-1/2" | 1.610 | nominal ID | 2.036 | 1.079 | 0.631 | 0.814 |
| EMT | 2" | 2.067 | nominal ID | 3.356 | 1.778 | 1.040 | 1.342 |
| EMT | 2-1/2" | 2.731 | nominal ID | 5.858 | 3.105 | 1.816 | 2.343 |
| EMT | 3" | 3.356 | nominal ID | 8.846 | 4.688 | 2.742 | 3.538 |
| EMT | 3-1/2" | 3.834 | nominal ID | 11.545 | 6.119 | 3.579 | 4.618 |
| EMT | 4" | 4.334 | nominal ID | 14.753 | 7.819 | 4.573 | 5.901 |
Wire dimensions used
The largest published diameter is used.
| Wire size | Cerrowire - THHN/THWN-2 spec sheet | Prysmian - THHN/THWN-2 High Speed SPEC 5290 | Encore Wire - SuperSlick Elite THHN spec sheet | Southwire - product pages THHN/THWN 14/12/10 AWG stranded | Priority Wire & Cable - Copper THHN/THWN-2 spec | Southwire - SIMpull THHN/THWN-2 SPEC 10000 | Largest (used) |
|---|---|---|---|---|---|---|---|
| 14 AWG | 0.111 | 0.109 | 0.109 | 0.113 | 0.120 | — | 0.120 |
| 12 AWG | 0.130 | 0.130 | 0.128 | 0.132 | 0.140 | — | 0.140 |
| 10 AWG | 0.164 | 0.161 | 0.161 | 0.165 | 0.170 | — | 0.170 |
| 8 AWG | 0.216 | 0.212 | 0.213 | — | 0.230 | 0.217 | 0.230 |
| 6 AWG | 0.254 | 0.248 | 0.249 | — | 0.250 | 0.253 | 0.254 |
| 4 AWG | 0.324 | 0.317 | 0.318 | — | 0.330 | 0.322 | 0.330 |
| 3 AWG | 0.352 | — | 0.346 | — | 0.360 | 0.350 | 0.360 |
| 2 AWG | 0.384 | 0.375 | 0.378 | — | 0.390 | 0.384 | 0.390 |
| 1 AWG | 0.446 | 0.427 | 0.435 | — | 0.450 | 0.441 | 0.450 |
| 1/0 AWG | 0.486 | 0.466 | 0.474 | — | 0.500 | 0.480 | 0.500 |
| 2/0 AWG | 0.532 | 0.509 | 0.518 | — | 0.540 | 0.524 | 0.540 |
| 3/0 AWG | 0.584 | 0.557 | 0.568 | — | 0.600 | 0.574 | 0.600 |
| 4/0 AWG | 0.642 | 0.612 | 0.624 | — | 0.660 | 0.627 | 0.660 |
| 250 kcmil | 0.711 | 0.694 | — | — | 0.720 | 0.684 | 0.720 |
| 300 kcmil | 0.766 | 0.747 | — | — | 0.766 | 0.753 | 0.766 |
| 350 kcmil | 0.817 | 0.797 | — | — | 0.830 | 0.803 | 0.830 |
| 400 kcmil | 0.864 | 0.842 | — | — | 0.864 | 0.848 | 0.864 |
| 500 kcmil | 0.949 | 0.925 | — | — | 0.960 | 0.931 | 0.960 |
| 600 kcmil | 1.051 | 1.024 | — | — | 1.051 | 1.030 | 1.051 |
| 750 kcmil | 1.156 | 1.126 | — | — | 1.170 | 1.132 | 1.170 |
| 1000 kcmil | 1.310 | 1.275 | — | — | 1.320 | 1.281 | 1.320 |
How to use this chart
Find the wire size in the left column and read across to the trade size of EMT you plan to use. Each cell is the most wires of that one size that fit at the 40% limit. For mixed sizes, use the calculator on the conduit fill chart page. Dimensions are shown below the chart, so you can check the math.
Frequently asked questions
How many 14 AWG wires fit in 1/2 inch EMT?
10 fourteen-gauge THHN/THWN-2 wires fit at the 40% limit by this method.
How many 10 AWG wires fit in 3/4 inch EMT?
9 ten-gauge wires fit at the 40% limit by this method.
How many wires can I put in 1 inch EMT?
It depends on the wire size. By this method, 1 inch EMT holds 22 twelve-gauge or 8 eight-gauge THHN/THWN-2 wires.
Is the inside diameter of EMT the same as the trade size?
No. Trade size is a name. 1/2 inch EMT has an inside diameter of about 0.622 inch.
Do ground wires count toward conduit fill?
Yes. Equipment grounding conductors take up space inside the conduit, so include them when you add wires.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.