PVC Conduit Fill Chart
PVC conduit has thicker walls than EMT, so it holds fewer wires. At the 40% limit, 3/4 inch Schedule 40 PVC holds 12 twelve-gauge wires by this method.
Last verified October 5, 2026
Fill result
PVC Schedule 40 conduit fill chart
Most THHN/THWN-2 conductors of one size at 40% fill, using minimum inside diameter.
The usual fill rule limits the wires to 53% of the conduit's internal area for one conductor, 31% for two and 40% for three or more. This page works out the area of the conduit and of each wire from the manufacturer dimensions below, then counts how many wires fit under the limit.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 9 | 16 | 28 | 49 | 67 | 113 | 161 | 251 | 435 |
| 12 AWG | 0.140 | 6 | 12 | 20 | 36 | 49 | 83 | 118 | 184 | 320 |
| 10 AWG | 0.170 | 4 | 8 | 13 | 24 | 33 | 56 | 80 | 125 | 217 |
| 8 AWG | 0.230 | 2 | 4 | 7 | 13 | 18 | 30 | 44 | 68 | 118 |
| 6 AWG | 0.254 | 2 | 3 | 6 | 11 | 15 | 25 | 36 | 56 | 97 |
| 4 AWG | 0.330 | 1 | 2 | 3 | 6 | 8 | 15 | 21 | 33 | 57 |
| 3 AWG | 0.360 | 1 | 1 | 3 | 5 | 7 | 12 | 17 | 27 | 48 |
| 2 AWG | 0.390 | 0 | 1 | 2 | 4 | 6 | 10 | 15 | 23 | 41 |
| 1 AWG | 0.450 | 0 | 1 | 1 | 3 | 4 | 8 | 11 | 17 | 30 |
| 1/0 AWG | 0.500 | 0 | 0 | 1 | 2 | 3 | 6 | 9 | 14 | 25 |
| 2/0 AWG | 0.540 | 0 | 0 | 1 | 2 | 3 | 5 | 7 | 12 | 21 |
| 3/0 AWG | 0.600 | 0 | 0 | 1 | 1 | 2 | 4 | 6 | 10 | 17 |
| 4/0 AWG | 0.660 | 0 | 0 | 0 | 1 | 2 | 3 | 5 | 8 | 14 |
PVC Schedule 80 conduit fill chart
Schedule 80 has thicker walls, so less room inside. Only trade sizes with two sources are listed.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 2" | 3" | 4" |
|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 7 | 13 | 23 | 98 | 220 | 387 |
| 12 AWG | 0.140 | 5 | 9 | 16 | 72 | 162 | 285 |
| 10 AWG | 0.170 | 3 | 6 | 11 | 48 | 110 | 193 |
| 8 AWG | 0.230 | 1 | 3 | 6 | 26 | 60 | 105 |
| 6 AWG | 0.254 | 1 | 3 | 5 | 21 | 49 | 86 |
| 4 AWG | 0.330 | 0 | 1 | 3 | 12 | 29 | 51 |
| 3 AWG | 0.360 | 0 | 1 | 2 | 10 | 24 | 43 |
| 2 AWG | 0.390 | 0 | 1 | 2 | 9 | 20 | 36 |
| 1 AWG | 0.450 | 0 | 0 | 1 | 6 | 15 | 27 |
| 1/0 AWG | 0.500 | 0 | 0 | 1 | 5 | 12 | 22 |
| 2/0 AWG | 0.540 | 0 | 0 | 1 | 4 | 10 | 19 |
| 3/0 AWG | 0.600 | 0 | 0 | 0 | 3 | 8 | 15 |
| 4/0 AWG | 0.660 | 0 | 0 | 0 | 3 | 7 | 12 |
PVC conduit dimensions used
Nominal and minimum inside diameters differ. The minimum is used where a maker publishes one.
| Conduit type | Trade size | Inside diameter used (in) | ID basis | Internal area (in²) | One wire, 53% (in²) | Two wires, 31% (in²) | Three or more, 40% (in²) |
|---|---|---|---|---|---|---|---|
| PVC Schedule 40 | 1/2" | 0.578 | minimum ID | 0.262 | 0.139 | 0.081 | 0.105 |
| PVC Schedule 40 | 3/4" | 0.780 | minimum ID | 0.478 | 0.253 | 0.148 | 0.191 |
| PVC Schedule 40 | 1" | 1.004 | minimum ID | 0.792 | 0.420 | 0.245 | 0.317 |
| PVC Schedule 40 | 1-1/4" | 1.335 | minimum ID | 1.400 | 0.742 | 0.434 | 0.560 |
| PVC Schedule 40 | 1-1/2" | 1.564 | minimum ID | 1.921 | 1.018 | 0.596 | 0.768 |
| PVC Schedule 40 | 2" | 2.021 | minimum ID | 3.208 | 1.700 | 0.994 | 1.283 |
| PVC Schedule 40 | 2-1/2" | 2.414 | minimum ID | 4.577 | 2.426 | 1.419 | 1.831 |
| PVC Schedule 40 | 3" | 3.008 | minimum ID | 7.106 | 3.766 | 2.203 | 2.843 |
| PVC Schedule 40 | 3-1/2" | 3.486 | minimum ID | 9.544 | 5.058 | 2.959 | 3.818 |
| PVC Schedule 40 | 4" | 3.961 | minimum ID | 12.323 | 6.531 | 3.820 | 4.929 |
| PVC Schedule 40 | 5" | 4.975 | minimum ID | 19.439 | 10.303 | 6.026 | 7.776 |
| PVC Schedule 40 | 6" | 5.986 | minimum ID | 28.143 | 14.916 | 8.724 | 11.257 |
| PVC Schedule 80 | 1/2" | 0.502 | minimum ID | 0.198 | 0.105 | 0.061 | 0.079 |
| PVC Schedule 80 | 3/4" | 0.698 | minimum ID | 0.383 | 0.203 | 0.119 | 0.153 |
| PVC Schedule 80 | 1" | 0.910 | minimum ID | 0.650 | 0.345 | 0.202 | 0.260 |
| PVC Schedule 80 | 2" | 1.881 | minimum ID | 2.779 | 1.473 | 0.861 | 1.112 |
| PVC Schedule 80 | 3" | 2.820 | minimum ID | 6.246 | 3.310 | 1.936 | 2.498 |
| PVC Schedule 80 | 4" | 3.737 | minimum ID | 10.968 | 5.813 | 3.400 | 4.387 |
| PVC Schedule 80 | 5" | 4.713 | minimum ID | 17.446 | 9.246 | 5.408 | 6.978 |
How to use this chart
Pick Schedule 40 or Schedule 80, find the wire size in the left column and read across to the trade size. We use the minimum inside diameter that PVC makers publish, which is the conservative choice. Schedule 80 has thicker walls and a smaller opening, so it holds fewer wires than Schedule 40 of the same size.
Frequently asked questions
How many 12 AWG wires fit in 1/2 inch PVC?
6 wires in Schedule 40 PVC at the 40% limit, by this method.
How many 12 AWG wires fit in 1 inch PVC?
20 wires in Schedule 40 PVC at the 40% limit, by this method.
Is Schedule 80 PVC conduit smaller inside than Schedule 40?
Yes. Both have the same outside diameter, but Schedule 80 has thicker walls, so less room inside.
Why does this page use the minimum inside diameter?
PVC walls and diameters vary within tolerance, and the minimum gives a count you can rely on.
Can I use the EMT numbers for PVC?
No. PVC has a smaller inside diameter than EMT of the same trade size, so use the PVC numbers.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.