Rigid Conduit Fill Chart
Rigid metal conduit is thick-wall threaded pipe. At the 40% limit, 3/4 inch RMC holds 14 twelve-gauge wires by this method, against 13 in EMT of the same trade size.
Last verified October 5, 2026
Fill result
Rigid metal conduit (RMC) fill chart
Most THHN/THWN-2 conductors of one size at 40% fill.
The usual fill rule limits the wires to 53% of the conduit's internal area for one conductor, 31% for two and 40% for three or more. This page works out the area of the conduit and of each wire from the manufacturer dimensions below, then counts how many wires fit under the limit.
| Wire size | OD used (in) | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 4" |
|---|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 11 | 19 | 31 | 53 | 73 | 120 | 172 | 265 | 455 |
| 12 AWG | 0.140 | 8 | 14 | 23 | 39 | 53 | 88 | 126 | 194 | 334 |
| 10 AWG | 0.170 | 5 | 9 | 15 | 26 | 36 | 60 | 85 | 132 | 227 |
| 8 AWG | 0.230 | 3 | 5 | 8 | 14 | 19 | 32 | 46 | 72 | 124 |
| 6 AWG | 0.254 | 2 | 4 | 7 | 12 | 16 | 26 | 38 | 59 | 101 |
| 4 AWG | 0.330 | 1 | 2 | 4 | 7 | 9 | 15 | 22 | 35 | 60 |
| 3 AWG | 0.360 | 1 | 2 | 3 | 5 | 8 | 13 | 19 | 29 | 50 |
| 2 AWG | 0.390 | 1 | 1 | 2 | 5 | 6 | 11 | 16 | 25 | 43 |
| 1 AWG | 0.450 | 0 | 1 | 2 | 3 | 5 | 8 | 12 | 18 | 32 |
| 1/0 AWG | 0.500 | 0 | 1 | 1 | 3 | 4 | 6 | 9 | 15 | 26 |
| 2/0 AWG | 0.540 | 0 | 0 | 1 | 2 | 3 | 5 | 8 | 13 | 22 |
| 3/0 AWG | 0.600 | 0 | 0 | 1 | 2 | 2 | 4 | 6 | 10 | 18 |
| 4/0 AWG | 0.660 | 0 | 0 | 1 | 1 | 2 | 3 | 5 | 8 | 15 |
Intermediate metal conduit (IMC) fill chart
IMC has a slightly larger inside diameter than rigid. Trade size 3/4 is not listed because the sources disagree.
| Wire size | OD used (in) | 1/2" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 4" |
|---|---|---|---|---|---|---|---|---|---|
| 14 AWG | 0.120 | 12 | 33 | 58 | 78 | 128 | 181 | 280 | 482 |
| 12 AWG | 0.140 | 8 | 24 | 42 | 57 | 94 | 133 | 205 | 354 |
| 10 AWG | 0.170 | 6 | 16 | 29 | 39 | 63 | 90 | 139 | 240 |
| 8 AWG | 0.230 | 3 | 9 | 15 | 21 | 34 | 49 | 76 | 131 |
| 6 AWG | 0.254 | 2 | 7 | 12 | 17 | 28 | 40 | 62 | 107 |
| 4 AWG | 0.330 | 1 | 4 | 7 | 10 | 16 | 24 | 37 | 63 |
| 3 AWG | 0.360 | 1 | 3 | 6 | 8 | 14 | 20 | 31 | 53 |
| 2 AWG | 0.390 | 1 | 3 | 5 | 7 | 12 | 17 | 26 | 45 |
| 1 AWG | 0.450 | 0 | 2 | 4 | 5 | 9 | 12 | 19 | 34 |
| 1/0 AWG | 0.500 | 0 | 1 | 3 | 4 | 7 | 10 | 16 | 27 |
| 2/0 AWG | 0.540 | 0 | 1 | 2 | 3 | 6 | 8 | 13 | 23 |
| 3/0 AWG | 0.600 | 0 | 1 | 2 | 3 | 5 | 7 | 11 | 19 |
| 4/0 AWG | 0.660 | 0 | 1 | 1 | 2 | 4 | 6 | 9 | 15 |
Rigid and IMC dimensions used
| Conduit type | Trade size | Inside diameter used (in) | ID basis | Internal area (in²) | One wire, 53% (in²) | Two wires, 31% (in²) | Three or more, 40% (in²) |
|---|---|---|---|---|---|---|---|
| Rigid metal conduit (RMC) | 1/2" | 0.632 | nominal ID | 0.314 | 0.166 | 0.097 | 0.125 |
| Rigid metal conduit (RMC) | 3/4" | 0.836 | nominal ID | 0.549 | 0.291 | 0.170 | 0.220 |
| Rigid metal conduit (RMC) | 1" | 1.063 | nominal ID | 0.887 | 0.470 | 0.275 | 0.355 |
| Rigid metal conduit (RMC) | 1-1/4" | 1.394 | nominal ID | 1.526 | 0.809 | 0.473 | 0.610 |
| Rigid metal conduit (RMC) | 1-1/2" | 1.624 | nominal ID | 2.071 | 1.098 | 0.642 | 0.829 |
| Rigid metal conduit (RMC) | 2" | 2.083 | nominal ID | 3.408 | 1.806 | 1.056 | 1.363 |
| Rigid metal conduit (RMC) | 2-1/2" | 2.489 | nominal ID | 4.866 | 2.579 | 1.508 | 1.946 |
| Rigid metal conduit (RMC) | 3" | 3.090 | nominal ID | 7.499 | 3.975 | 2.325 | 3.000 |
| Rigid metal conduit (RMC) | 3-1/2" | 3.570 | nominal ID | 10.010 | 5.305 | 3.103 | 4.004 |
| Rigid metal conduit (RMC) | 4" | 4.050 | nominal ID | 12.882 | 6.828 | 3.994 | 5.153 |
| Rigid metal conduit (RMC) | 5" | 5.073 | nominal ID | 20.212 | 10.713 | 6.266 | 8.085 |
| Rigid metal conduit (RMC) | 6" | 6.093 | nominal ID | 29.158 | 15.454 | 9.039 | 11.663 |
| Intermediate metal conduit (IMC) | 1/2" | 0.660 | nominal ID | 0.342 | 0.181 | 0.106 | 0.137 |
| Intermediate metal conduit (IMC) | 1" | 1.105 | nominal ID | 0.959 | 0.508 | 0.297 | 0.384 |
| Intermediate metal conduit (IMC) | 1-1/4" | 1.448 | nominal ID | 1.647 | 0.873 | 0.510 | 0.659 |
| Intermediate metal conduit (IMC) | 1-1/2" | 1.683 | nominal ID | 2.225 | 1.179 | 0.690 | 0.890 |
| Intermediate metal conduit (IMC) | 2" | 2.150 | nominal ID | 3.631 | 1.924 | 1.125 | 1.452 |
| Intermediate metal conduit (IMC) | 2-1/2" | 2.557 | nominal ID | 5.135 | 2.722 | 1.592 | 2.054 |
| Intermediate metal conduit (IMC) | 3" | 3.176 | nominal ID | 7.922 | 4.199 | 2.456 | 3.169 |
| Intermediate metal conduit (IMC) | 3-1/2" | 3.671 | nominal ID | 10.584 | 5.610 | 3.281 | 4.234 |
| Intermediate metal conduit (IMC) | 4" | 4.166 | nominal ID | 13.631 | 7.224 | 4.226 | 5.452 |
How to use this chart
Find the wire size and read across for each trade size, for rigid (RMC) and intermediate (IMC) conduit. IMC has thinner walls than rigid, so it has a slightly larger inside diameter at the same trade size. Rigid trade sizes also run a little larger inside than EMT. Trade size 3/4 inch IMC is left out because the sources disagree on its dimensions.
Frequently asked questions
What is the difference between rigid and IMC conduit?
IMC has thinner walls than rigid, so it weighs less and has a slightly larger opening at the same trade size.
How many 10 AWG wires fit in 1 inch rigid conduit?
15 wires at the 40% limit, by this method.
Is rigid conduit the same as EMT?
No. EMT is thin-wall tubing and rigid conduit is thick-wall pipe with threaded fittings.
Why is 3/4 inch IMC not listed?
We only publish sizes that two sources agree on, and the sources disagree on this one.
Do the same fill limits apply to rigid conduit?
Yes. The 53%, 31% and 40% limits apply to all the common conduit types.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.