Rigid Conduit Fill Chart

Rigid metal conduit is thick-wall threaded pipe. At the 40% limit, 3/4 inch RMC holds 14 twelve-gauge wires by this method, against 13 in EMT of the same trade size.

Last verified October 5, 2026

Download PDF
Conduit fill calculator
Wires in the conduit

Fill result

0 % full

Rigid metal conduit (RMC) fill chart

Most THHN/THWN-2 conductors of one size at 40% fill.

The usual fill rule limits the wires to 53% of the conduit's internal area for one conductor, 31% for two and 40% for three or more. This page works out the area of the conduit and of each wire from the manufacturer dimensions below, then counts how many wires fit under the limit.

Most THHN/THWN-2 conductors of one size that fit in Rigid metal conduit (RMC) at the 40% fill limit
Wire sizeOD used (in)1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"4"
14 AWG0.1201119315373120172265455
12 AWG0.14081423395388126194334
10 AWG0.170591526366085132227
8 AWG0.2303581419324672124
6 AWG0.2542471216263859101
4 AWG0.3301247915223560
3 AWG0.3601235813192950
2 AWG0.3901125611162543
1 AWG0.450012358121832
1/0 AWG0.50001134691526
2/0 AWG0.54000123581322
3/0 AWG0.60000122461018
4/0 AWG0.6600011235815

Intermediate metal conduit (IMC) fill chart

IMC has a slightly larger inside diameter than rigid. Trade size 3/4 is not listed because the sources disagree.

Most THHN/THWN-2 conductors of one size that fit in Intermediate metal conduit (IMC) at the 40% fill limit
Wire sizeOD used (in)1/2"1"1-1/4"1-1/2"2"2-1/2"3"4"
14 AWG0.12012335878128181280482
12 AWG0.140824425794133205354
10 AWG0.17061629396390139240
8 AWG0.230391521344976131
6 AWG0.254271217284062107
4 AWG0.3301471016243763
3 AWG0.360136814203153
2 AWG0.390135712172645
1 AWG0.45002459121934
1/0 AWG0.50001347101627
2/0 AWG0.5400123681323
3/0 AWG0.6000123571119
4/0 AWG0.660011246915

Rigid and IMC dimensions used

Conduit typeTrade sizeInside diameter used (in)ID basisInternal area (in²)One wire, 53% (in²)Two wires, 31% (in²)Three or more, 40% (in²)
Rigid metal conduit (RMC)1/2"0.632nominal ID0.3140.1660.0970.125
Rigid metal conduit (RMC)3/4"0.836nominal ID0.5490.2910.1700.220
Rigid metal conduit (RMC)1"1.063nominal ID0.8870.4700.2750.355
Rigid metal conduit (RMC)1-1/4"1.394nominal ID1.5260.8090.4730.610
Rigid metal conduit (RMC)1-1/2"1.624nominal ID2.0711.0980.6420.829
Rigid metal conduit (RMC)2"2.083nominal ID3.4081.8061.0561.363
Rigid metal conduit (RMC)2-1/2"2.489nominal ID4.8662.5791.5081.946
Rigid metal conduit (RMC)3"3.090nominal ID7.4993.9752.3253.000
Rigid metal conduit (RMC)3-1/2"3.570nominal ID10.0105.3053.1034.004
Rigid metal conduit (RMC)4"4.050nominal ID12.8826.8283.9945.153
Rigid metal conduit (RMC)5"5.073nominal ID20.21210.7136.2668.085
Rigid metal conduit (RMC)6"6.093nominal ID29.15815.4549.03911.663
Intermediate metal conduit (IMC)1/2"0.660nominal ID0.3420.1810.1060.137
Intermediate metal conduit (IMC)1"1.105nominal ID0.9590.5080.2970.384
Intermediate metal conduit (IMC)1-1/4"1.448nominal ID1.6470.8730.5100.659
Intermediate metal conduit (IMC)1-1/2"1.683nominal ID2.2251.1790.6900.890
Intermediate metal conduit (IMC)2"2.150nominal ID3.6311.9241.1251.452
Intermediate metal conduit (IMC)2-1/2"2.557nominal ID5.1352.7221.5922.054
Intermediate metal conduit (IMC)3"3.176nominal ID7.9224.1992.4563.169
Intermediate metal conduit (IMC)3-1/2"3.671nominal ID10.5845.6103.2814.234
Intermediate metal conduit (IMC)4"4.166nominal ID13.6317.2244.2265.452

How to use this chart

Find the wire size and read across for each trade size, for rigid (RMC) and intermediate (IMC) conduit. IMC has thinner walls than rigid, so it has a slightly larger inside diameter at the same trade size. Rigid trade sizes also run a little larger inside than EMT. Trade size 3/4 inch IMC is left out because the sources disagree on its dimensions.

Frequently asked questions

What is the difference between rigid and IMC conduit?

IMC has thinner walls than rigid, so it weighs less and has a slightly larger opening at the same trade size.

How many 10 AWG wires fit in 1 inch rigid conduit?

15 wires at the 40% limit, by this method.

Is rigid conduit the same as EMT?

No. EMT is thin-wall tubing and rigid conduit is thick-wall pipe with threaded fittings.

Why is 3/4 inch IMC not listed?

We only publish sizes that two sources agree on, and the sources disagree on this one.

Do the same fill limits apply to rigid conduit?

Yes. The 53%, 31% and 40% limits apply to all the common conduit types.

Disclaimer. Reference only. The adopted electrical code and the manufacturer's data govern. Have installations designed and inspected by a licensed electrician. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.

Last verified October 5, 2026. How we verify explains our two-source rule and what we leave out.

Insulated wire diameters differ between manufacturers, so each maker's published value is listed on the page and the largest is used. Counts can therefore be lower than the code's tabulated numbers, which use their own wire areas.

Sources used on this page
  • Wheatland Tube - EMT and Conduit Brochure
  • Nucor Tubular Products - Electrunite EMT spec sheet
  • Western Tube - Electrical Conduit Brochure
  • Wheatland Tube - Rigid Metal Conduit Submittal Sheet
  • Allied Tube & Conduit - Rigid Steel Conduit
  • Allied Tube & Conduit - IMC Specification Sheet
  • Carlon
  • JM Eagle - Electrical Conduit
  • Team EJP / EJ Prescott - PVC Schedule 40 & 80 conduit pipe sheet
  • Cerrowire - THHN/THWN-2 spec sheet
  • Prysmian - THHN/THWN-2 High Speed SPEC 5290
  • Encore Wire - SuperSlick Elite THHN spec sheet
  • Southwire - product pages THHN/THWN 14/12/10 AWG stranded
  • Priority Wire & Cable - Copper THHN/THWN-2 spec
  • Southwire - SIMpull THHN/THWN-2 SPEC 10000
  • Southwire - XHHW-2 spec 10005
  • Cerrowire - XHHW-2 spec sheet
  • Southwire - SIMpull XHHW-2 SPEC 10006