Natural Gas Pipe Sizing Chart
A natural gas pipe sizing chart gives the BTU a pipe can carry over each length. For example, 3/4 inch steel carries about 152 MBH over 50 feet and 1 inch carries about 286 MBH, at a 0.5 inch water column drop.
Last verified October 5, 2026
Important. Estimate only. Gas piping must be sized, installed and inspected by a licensed professional under your local code and the appliance maker's instructions.
Smallest pipe that meets the load
Natural gas pipe sizing chart, steel, 0.5 in. w.c. drop
Sizing equation for low-pressure systems: D = Q0.381 ÷ (19.17 × (ΔH ÷ (Cr × L))0.206), where D is inside diameter in inches, Q is flow in cubic feet per hour, ΔH is the pressure drop in inches of water column, L is the pipe length in feet and Cr is 0.6094 for natural gas or 1.2462 for propane. Capacities below invert the same equation and are shown in thousands of BTU per hour. Natural gas is taken at 1,000 BTU per cubic foot and propane at 2,516.
| Pipe length | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 4" |
|---|---|---|---|---|---|---|---|---|---|
| 10 ft | 173 | 362 | 682 | 1,401 | 2,100 | 4,046 | 6,450 | 11,407 | 23,276 |
| 20 ft | 119 | 249 | 469 | 963 | 1,443 | 2,781 | 4,434 | 7,841 | 16,001 |
| 30 ft | 96 | 200 | 377 | 774 | 1,159 | 2,234 | 3,561 | 6,298 | 12,851 |
| 40 ft | 82 | 171 | 322 | 662 | 992 | 1,912 | 3,048 | 5,391 | 11,000 |
| 50 ft | 72 | 152 | 286 | 587 | 880 | 1,695 | 2,702 | 4,778 | 9,750 |
| 60 ft | 66 | 137 | 259 | 532 | 797 | 1,536 | 2,448 | 4,329 | 8,834 |
| 80 ft | 56 | 118 | 222 | 455 | 682 | 1,314 | 2,095 | 3,706 | 7,562 |
| 100 ft | 50 | 104 | 196 | 403 | 605 | 1,165 | 1,857 | 3,285 | 6,702 |
| 125 ft | 44 | 92 | 174 | 358 | 536 | 1,033 | 1,646 | 2,911 | 5,941 |
| 150 ft | 40 | 84 | 158 | 324 | 486 | 936 | 1,492 | 2,638 | 5,383 |
| 200 ft | 34 | 72 | 135 | 277 | 416 | 801 | 1,277 | 2,258 | 4,608 |
Natural gas, type K copper tube, 0.5 in. w.c. drop
Copper tube sizes are named by outside diameter, so the inside diameter is smaller than the name.
| Pipe length | 3/8" | 1/2" | 5/8" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" |
|---|---|---|---|---|---|---|---|---|
| 10 ft | 55 | 112 | 196 | 278 | 594 | 1,069 | 1,686 | 3,514 |
| 20 ft | 38 | 77 | 135 | 191 | 408 | 735 | 1,159 | 2,416 |
| 30 ft | 30 | 62 | 108 | 153 | 328 | 590 | 931 | 1,940 |
| 40 ft | 26 | 53 | 93 | 131 | 281 | 505 | 797 | 1,661 |
| 50 ft | 23 | 47 | 82 | 116 | 249 | 448 | 706 | 1,472 |
| 60 ft | 21 | 43 | 74 | 105 | 225 | 406 | 640 | 1,334 |
| 80 ft | 18 | 36 | 64 | 90 | 193 | 347 | 548 | 1,142 |
| 100 ft | 16 | 32 | 56 | 80 | 171 | 308 | 486 | 1,012 |
| 125 ft | 14 | 29 | 50 | 71 | 152 | 273 | 430 | 897 |
| 150 ft | 13 | 26 | 45 | 64 | 137 | 247 | 390 | 813 |
| 200 ft | 11 | 22 | 39 | 55 | 118 | 212 | 334 | 696 |
Natural gas, Schedule 40 steel, 1.0 in. w.c. drop
For systems where the supply pressure allows a larger drop.
| Pipe length | 1/2" | 3/4" | 1" | 1-1/4" | 1-1/2" | 2" | 2-1/2" | 3" | 4" |
|---|---|---|---|---|---|---|---|---|---|
| 10 ft | 252 | 527 | 992 | 2,038 | 3,054 | 5,885 | 9,382 | 16,593 | 33,859 |
| 20 ft | 173 | 362 | 682 | 1,401 | 2,100 | 4,046 | 6,450 | 11,407 | 23,276 |
| 30 ft | 139 | 291 | 548 | 1,125 | 1,686 | 3,249 | 5,180 | 9,161 | 18,694 |
| 40 ft | 119 | 249 | 469 | 963 | 1,443 | 2,781 | 4,434 | 7,841 | 16,001 |
| 50 ft | 105 | 221 | 416 | 854 | 1,279 | 2,465 | 3,930 | 6,950 | 14,183 |
| 60 ft | 96 | 200 | 377 | 774 | 1,159 | 2,234 | 3,561 | 6,298 | 12,851 |
| 80 ft | 82 | 171 | 322 | 662 | 992 | 1,912 | 3,048 | 5,391 | 11,000 |
| 100 ft | 72 | 152 | 286 | 587 | 880 | 1,695 | 2,702 | 4,778 | 9,750 |
| 125 ft | 64 | 134 | 253 | 520 | 780 | 1,502 | 2,395 | 4,235 | 8,642 |
| 150 ft | 58 | 122 | 229 | 471 | 706 | 1,361 | 2,170 | 3,837 | 7,830 |
| 200 ft | 50 | 104 | 196 | 403 | 605 | 1,165 | 1,857 | 3,285 | 6,702 |
How to use this chart
Find the pipe length in the first column, read across to the pipe size and compare the number in thousands of BTU per hour with the total load of your appliances. Measure to the farthest appliance and use that length for the whole run. Always round up to the next larger size. The tables use the low-pressure sizing equation shown above them.
Frequently asked questions
How much gas will 3/4 inch pipe carry?
About 152 MBH of natural gas over 50 feet at a 0.5 inch water column drop, by this method.
How much gas will 1/2 inch pipe carry?
About 119 MBH over 20 feet at a 0.5 inch water column drop. It drops as the run gets longer.
What is an inch of water column?
A small unit of pressure. Low-pressure home gas systems run at around 7 inches of water column, and the sizing drop is a half inch to one inch of that.
Does the length include fittings?
The length you enter should be the longest run from the meter to the farthest appliance. Some codes add allowances for fittings, so ask your inspector.
Why does a longer run need a bigger pipe?
Friction builds up along the pipe, so more length means more pressure lost for the same flow. A bigger pipe has less friction.
Explore the whole Calcs family here.
Tell us which value looks off and we will check it against the sources. Report an issue
Tell us what you looked for. Suggest a chart
Disclaimer. Estimate only. Gas piping must be sized, installed and inspected by a licensed professional under your local code and the appliance maker's instructions. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.