Gas Pipe Sizing Calculator and Chart

Gas pipe size depends on the load, the length of the run and the pressure drop you allow. For example, 3/4 inch steel pipe carries about 152,000 BTU per hour of natural gas over 50 feet at a half inch of water column drop.

Last verified October 5, 2026

Important. Estimate only. Gas piping must be sized, installed and inspected by a licensed professional under your local code and the appliance maker's instructions.

Download PDF
Gas pipe sizing calculator

Smallest pipe that meets the load

1 inch

Natural gas capacity, Schedule 40 steel, 0.5 in. w.c. drop

Thousands of BTU per hour (MBH) a pipe can carry over the length shown. Always round up to the next size.

Sizing equation for low-pressure systems: D = Q0.381 ÷ (19.17 × (ΔH ÷ (Cr × L))0.206), where D is inside diameter in inches, Q is flow in cubic feet per hour, ΔH is the pressure drop in inches of water column, L is the pipe length in feet and Cr is 0.6094 for natural gas or 1.2462 for propane. Capacities below invert the same equation and are shown in thousands of BTU per hour. Natural gas is taken at 1,000 BTU per cubic foot and propane at 2,516.

Natural gas, Schedule 40 steel pipe, MBH
Pipe length1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"4"
10 ft1733626821,4012,1004,0466,45011,40723,276
20 ft1192494699631,4432,7814,4347,84116,001
30 ft962003777741,1592,2343,5616,29812,851
40 ft821713226629921,9123,0485,39111,000
50 ft721522865878801,6952,7024,7789,750
60 ft661372595327971,5362,4484,3298,834
80 ft561182224556821,3142,0953,7067,562
100 ft501041964036051,1651,8573,2856,702
125 ft44921743585361,0331,6462,9115,941
150 ft40841583244869361,4922,6385,383
200 ft34721352774168011,2772,2584,608

Propane capacity, Schedule 40 steel, 0.5 in. w.c. drop

Propane, Schedule 40 steel pipe, MBH
Pipe length1/2"3/4"1"1-1/4"1-1/2"2"2-1/2"3"4"
10 ft2966191,1662,3943,5886,91411,02319,49339,778
20 ft2034258011,6462,4674,7537,57713,40027,345
30 ft1633426441,3221,9813,8176,08610,76221,962
40 ft1402925511,1321,6963,2675,2099,21218,798
50 ft1242594881,0031,5032,8964,6178,16516,662
60 ft1122354429091,3622,6244,1847,39915,098
80 ft962013797781,1662,2463,5816,33312,923
100 ft851783366891,0331,9913,1745,61311,454
125 ft751582986119161,7652,8134,97510,152
150 ft681432705548301,5992,5494,5089,199
200 ft591222314747101,3692,1823,8597,874

How to use this calculator

Enter the gas, the total BTU per hour of your appliances, the longest run in feet, the pressure drop and the pipe material. The calculator converts BTU to cubic feet per hour, solves for the minimum inside diameter and returns the smallest standard size that meets it, rounding up. The capacity tables below invert the same equation. Always round up to the next size, and have a licensed professional size and inspect the system.

Frequently asked questions

What size gas pipe do I need for 100,000 BTU?

It depends on the length of the run. By this method, 1/2 inch steel carries about 119 MBH over 20 feet, so 100,000 BTU fits only on a short run, while 3/4 inch carries about 152 MBH over 50 feet. Enter your load and length above to check.

How do you size a gas line?

Add up the BTU of every appliance, find the longest run to the farthest one, pick an allowed pressure drop and choose the pipe size that carries the total over that length.

How do I convert BTU to cubic feet of gas?

Divide BTU per hour by the heating value of the gas. Natural gas is about 1,000 BTU per cubic foot and propane is about 2,516.

Is gas pipe sized by the whole load or one appliance?

The pipe feeding several appliances must carry their combined load. Each branch can be smaller, down to the one appliance it serves.

Why is propane pipe smaller than natural gas pipe?

Propane has about two and a half times the heating value per cubic foot, so the same BTU needs less flow and a smaller pipe at low pressure.

Does this calculator cover CSST or high pressure systems?

No. It covers low-pressure steel pipe and copper tube. CSST and high-pressure systems have their own sizing tables from the maker.

Disclaimer. Estimate only. Gas piping must be sized, installed and inspected by a licensed professional under your local code and the appliance maker's instructions. Charts & Specs is an independent reference site. It is not affiliated with any manufacturer, standards body or code organization, and it uses brand and standard names only to identify what a value applies to.

Last verified October 5, 2026. How we verify explains our two-source rule and what we leave out.

The pipe-sizing constants (Cr of 0.6094 for natural gas and 1.2462 for propane, and the 0.381, 0.206 and 19.17 terms) were checked in the adopted fuel gas code text as reproduced by Seattle and the ICC. Those copies come from the same code text, so they are one source seen several times, not independent confirmation.

Sources used on this page
  • Seattle fuel gas code, chapter 4 (adopted IFGC text)
  • ICC-hosted IFGC chapter 4
  • H2X Engineering calculator
  • PHCP Pros
  • Copper Development Association tube tables
  • Wheatland Tube ASTM A53 pipe table
  • Engineering ToolBox